VENTING
VENT DAMPERS - Any vent damper, whether it is operated
thermally or otherwise must be removed if its use inhibits proper
drafting of the water heater.
Thermally Operated Vent Dampers: This gas-fired water
heater has a thermal efciency at or above 80% which may
produce a relatively low ue gas temperature. Such temperatures
may not be high enough to properly open thermally operated
vent dampers. This would cause spillage of the ue gases and
may cause carbon monoxide poisoning.
Vent dampers must bear evidence of certication as complying
with the current edition of the American National Standard
ANSI Z21.66/CGA 6.14, cover electrically and mechanically
actuated vent dampers). Before installation of any vent damper,
consult your local Sears Service Center or the local gas supplier
for further information.
To insure proper venting of this gas-red water heater, the correct
vent pipe diameter must be utilized. Any additions or deletions
of other gas appliances on a common vent with this water heater
may adversely affect the operation of the water heater. Consult
your gas supplier if any such changes are planned.
For proper venting in certain installations, a larger diameter vent
pipe may be necessary. Consult your local Sears Service Center
or gas supplier to aid you in determining the proper venting for
your water heater from the vent tables in the current edition of
the National Fuel Gas Code ANSI Z223.1/NFPA 54.
Periodically check the venting system for signs of obstruction or
deterioration and replace if needed.
The combustion and ventilation air ow must not be obstructed.
The water heater with draft hood installed must be connected
to a chimney or listed vent pipe system, which terminates to the
outdoors. Never operate the water heater unless it is vented
to the outdoors and has adequate air supply to avoid risks of
improper operation, explosion or asphyxiation.
For proper draft hood attachment, the draft hood legs may
be angled slightly inward.
Place the draft hood legs in the receiving holes on the top
of the water heater. The legs will snap in the holes to give a
tight t. Secure the legs of the draft hood with the supplied
draft hood brackets.
Place the vent pipe over the draft hood. With the vent pipe
in position, drill a small hole through both the vent pipe and
draft hood. Secure them together with a sheet metal screw,
see Figure 18.
FIGURE 18.
Obstructed or deteriorated vent systems may present serious
health risk or asphyxiation.
The vent pipe from the water heater must be no less than the
diameter of the draft hood outlet on the water heater and must
slope upward at least 1/4 inch per linear foot (21 mm per meter),
see Figure 19.
FIGURE 19.
All vent gases must be completely vented to the outdoors of the
structure (dwelling). Install only the draft hood provided with the
new water heater and no other draft hood.
Vent pipes must be secured at each joint with sheet metal screws.
There must be a minimum of 6 inches (153 mm) clearance
between single wall vent pipe and any combustible material.
Fill and seal any clearance between single wall vent pipe
and combustible material with mortar mix, cement, or other
noncombustible substance. For other than single wall, follow
vent pipe manufacturer’s clearance specications. To insure a
tight t of the vent pipe in a brick chimney, seal around the vent
pipe with mortar mix cement.
Failure to have required clearances between vent piping and
combustible material will result in a re hazard.
Be sure vent pipe is properly connected to prevent escape of
dangerous ue gases which could cause deadly asphyxiation.